
Reducing Nosocomial Infections in ORs
By Farhad Memarzadeh, PhD, PE and Andy Manning, PhD

Figure 1. Source and routes of infection in the
operating room5 |
The National Institutes of Health (NIH) Office of Research Services, Division
of Engineering Services, conducted an extensive study on the issue of operating
room (OR) ventilation systems and their effect on the protection of the surgical
site.
The risk of nosocomial infection is present in all surgical procedures, but
can be particularly serious in certain operations, such as joint replacement.
The many factors that influence infection are shown in Figure 1.
The standards suggested for air conditioning systems for ORs in different
countries vary widely in content and recommendations and are often based on old
research. For example, the ASHRAE Handbook1 is based on work
originally carried out in the 1950s. As a point of reference, the ASHRAE
Handbook suggests that "the delivery of air from the ceiling, with a
downward movement to several exhaust inlets located on opposite walls, is
probably the most effective air movement pattern for maintaining the
concentration at an acceptable level."1

click here to view tables.
The handbook indicates that the temperature range should be between 62
degrees Fahrenheit (16.67 Celsius) and 80 degrees F (26.67 C), and that positive
pressurization should be maintained. It also suggests that the air should be
exhausted or returned from at least two locations near the floor. It suggests
that supply diffusers should be of the unidirectional type and that
high-induction ceiling or sidewall diffusers should be avoided. The recommended
ACH is 15 ACH for systems that use all outdoor air and 25 ACH for re-circulating
air systems.

Figure 2. Layout of baseline operating room --Mayo
stand view |
Some studies have been published which consider the relative merits of
different systems, such as Lidwell2 and Schmidt.3 However,
since they do not include specific system design data, it is difficult to
establish definitive recommendations. Further, while laminar flow systems
provided lower general concentration levels in the room, they are sometimes
blamed for higher infection rates than more conventional systems, for example,
Salvati et al.4 The theory put forward by Lewis5 is that
laminar flow systems cause impingement on the wound site. However, with Schmidt
defining a laminar system as having velocities of at least 90 fpm (0.45m/s),
this probably is due to high supply velocities.
The aforementioned studies were experiment based; however, an alternative
technique, Computational Fluid Dynamics (CFD), sometimes known as airflow
modeling, has been proved to be very powerful and efficient in research projects
involving parametric study on room airflow and contaminant dispersion (Ziang, et
al.6 and Haghighat et al.7) In the study documented here,
airflow modeling is used to consider the dispersion of squame-sized particles
(which are recognized as the main transport mechanism of bacteria in operating
rooms (Woods, et al.)8 under various ventilation system-design
conditions. To establish the relative ranking of the different systems, two
target areas of concern are considered: the surgical site and the top surface of
the back table where instruments are located.
Methodology
The
CFD and particle tracking routine methodology are described in detail in
Memarzadeh and Manning.9 (They are not included here because of space
limitations. A copy of the paper is available at: http://des.od.nih.gov/eWeb/research/farhad/index.htm.)
Outline of Base Model
A typical OR layout was considered for the baseline model. The room measured
20 feet (6.1m) by 20 feet (6.1m) by 12 feet (3.66m) high; general features are
given in Figure 2 and Table 1. The room's layout was agreed upon by a panel of
physicians and engineers. The total heat dissipated in the room was 2166W.
Model considerations
Several ventilation systems were considered in this study and are shown in
Table 2. These systems approximately replicate those outlined in Schmidt.3
Models of the various diffuser types considered in this project were all
validated prior to the room parametric study against manufacturers data.
Contamination consideration

Figure 4. Flow Field in Case 1 |
Squames are cells which are released from exposed regions of the surgery
staff and patient, for example, neck, face, etc., and are the primary transport
mechanism for bacteria in the OR. They are approximately 25 microns (mm) by 3 to
5 microns thick. Approximately 1.15 by 106 to 0.9 to 108 squames are generated
during a typical (two-hour to four-hour) procedure.10 In this study,
the squame particles would be tracked to see how many hit the back table, shown
in Figure 3, or the surgical site. The surgical site was taken as a 1-foot
(0.3m) by 1-foot (0.3m) square with the surface temperature at 100 degrees F
(37.78C), and is shown in Figure 3.
A representative number of particles was introduced from three arrays of
sources in the CFD models. The locations and sizes of the sources, designated as
Main, Nurse and Surgery, are shown in Table 3. As the particles could readily
pass to the instruments at this point, the surgery source/top surface of back
table target analysis was not performed in this study.
Results
There are three potential particle outcomes:
- The particle exits the room via exhaust grilles
- The particle strikes the surgical site or top surface of back table.
- The particle remains in the room at the time where particle tracking is
stopped (one hour)
- Percentage of particles removed by ventilation varying with time

Figure 5. Thermal Plume From Surgical Site in Case 2
(Laminar Design) |
Table 4 shows there is a wide range of particle removal effectiveness. Cases
that have the same ACH show marked differences in terms of the percentage of
particles removed via ventilation. For example, Case 10 demonstrates a more
effective removal of particles than Case 1.The reason is that the ventilation
system in Case 1 results in the formation of two large re-circulations in the
room where particles can become trapped; this is illustrated in Figure 4. In
Case 10 the ventilation system works with the thermal plume in the center of the
room in driving the particles up to the high level exhausts. Taking Cases 3, 4,
5, 6 and 9 as a group that adopts the same general approach to ventilation, the
percentage vented from all locations becomes more uniform on increasing ACH and
supply array size. The reason is, for the smaller laminar arrays, the areas
outside the direct influence of the supply have very low velocity flow fields,
and particles are more likely to drop to the floor via gravity.
Percentage of Particles, Which Hit Surgical Site or Top Surface of Back
Table

Figure 6. Flow Field in Case 9 |
Table 5 shows that the percentages of particles which hit the surgical site
from the main or nurse sites are low (less than 1 percent) because of the
relative dominance of the thermal plume caused by the surgical site. For
example, Figure 5 shows such a plume for Case 2. It is only when the particles
are released close to the site, in particular, the surgery source, that the
percentage becomes significant. It is also clear that ACH is not as significant
in the surgery source/surgical site analysis as design of the ventilation
system. In particular, a lower percentage of particles hit the site in Case 4,
which has an ACH of 20, than Case 2, which has an ACH of 150.
The results also show, with the exception of Case 11, the percentage of
particles that hit the back table from the main or nurse sites is relatively
low. In Case 11, the particles are blown onto the table. The results for Cases
4, 5 and 6 indicate that a mixture of exhaust location levels is better than low
or high only. Finally, the cases which can be placed together in a laminar flow
type group, namely, Cases 2, 3, 4, 5, 6 and 9, show lower strike rates than the
other systems. In fact, Cases 4 and 9 represent the lowest strike percentages of
all the cases considered.
Conclusions and Discussion
Conclusions of the study are:
- Cases which have the same ACH show marked differences in terms of the
percentage of particles removed via ventilation.
- The practice of increasing ACH to high levels results in excellent removal
of particles via ventilation, but it does not necessarily mean that the
percentage of particles which strike critical surfaces will continue to
decrease.
- The percentages of particles which hit the surgical site from the Main or
Nurse sites are low (less than 1 percent). This is because of the relative
dominance of the thermal plume associated with the warm surgical site. Only
when the particles are released close to the site, in particular, the
surgery source, does the percentage become significant.
- ACH is not as significant as the design of the ventilation system. In
particular, a lower percentage of particles hits the site in a case which
has an ACH of 20, than one which has an ACH of 150.
- In a system which provides a laminar flow regime, a mixture of exhaust
location levels works better than either low or high level locations only.
However, the difference is not significant enough that the low- or
high-level location systems are not viable options.
- Systems that provide laminar flow regimes represent the best option for an
operating room in terms of contamination control; however, care needs to be
taken in the sizing of the laminar flow array. A face velocity of around 30
to 35 fpm (0.15 to 0.18 m/s) is sufficient from the laminar diffuser array
provided that the array size itself is set correctly.
To expand on the issue of diffuser array size, it appears that the main
factor in the design of the ventilation system is the control of the central
region of the OR. In particular, the operating lights and surgical staff
represent a large heat density in the middle of the room. Particulates could get
caught in buoyant plumes created by these heat-dissipating objects, at which
point control of them is lost; however, if a laminar flow type system is
employed, the particles are instead driven by the flow to the exhaust. Ideally
then, the array size should be large enough to cover the main heat dissipating
objects.
This is illustrated in Figure 6, which shows the flow field for Case 9.
Further, another factor is the thermal plume created by the surgical site,
shown for Case 2 in Figure 5.A laminar flow regime which provides air at 30-35
fpm (0.15 to 0.18 m/s) ensures that particles are not impinged on the surgical
site, a danger highlighted by Lewis5 as the thermal plume should be
sufficient to protect the surgical site.
Farhad Memarzadeh, PhD, PE, is chief of technical resources in the Office
of Research Services, Division of Engineering Services at the National
Institutes of Health in Bethesda, Md. Andy Manning, PhD, is director of
engineering for Flomerics, Inc. of Southboro, Mass.
|